Wiring and signal path

Pick a compartment and run an unlock to follow the command from the app to the lock. You can also simulate a mains or internet outage.

Data Power 12 V / 5 V Active path Bus termination
Choose a compartment, then run the unlock.

Connection list

FromToCable
Mains 230 VIEC inlet (switch + fuse) → PSU 12 V 5 A3-core mains cable
PSU 12 V outputDC UPS module → battery and load output1 mm², red/black
UPS load output5 A fuse → board 1 power input1 mm², red/black
Board 1 → 2 → 3Cascade ports P1 / P2Supplied 4-wire cable
Raspberry Pi USBUSB-RS485 converterDirect plug
Converter A, B, GNDBoard 1 A, B, GNDTwisted pair (e.g. Cat5e pair)
UPS load outputBuck 12→5 V → Raspberry Pi USB-C5 V 3 A
Each board channelIts lock (coil + door sensor)Supplied harness, via ducts

Five rules for a first-time-right install

  1. Give each board a unique address (01, 02, 03) with its DIP switches or buttons.
  2. Don't swap A and B. If nothing answers, check this first.
  3. Tie every ground (GND) together: PSU, boards and converter.
  4. Fit a 120 Ω termination on the last board of the chain. It's often on-board, enabled by a jumper.
  5. Fuse the 12 V output at 5 A.
Only one lock fires at a time. A pulse draws about 1 A for 0.5 s, so a 5 A supply leaves good margin. Never trigger several locks at once from the software.